Sign in or register

My Eezglobal

My shopping cart

   
Business & Industrial> Building Engineering Supplies> Refrigerating Dryer>
239848:15C Refrigerating Dryer Air Compressor Refrigerated Freeze Dryer 220V
Unit:
set
Price:
735.00$
Weight:
79.00kg
QTY:
     

Similar products

239698:10C Refrigerating Dryer Air Compressor Refrigerated Freeze Dryer

239847:7.5C Refrigerating Dryer Air Compressor Refrigerated Freeze Dryer

033181:20C Refrigerating Dryer Air Compressor Refrigerated Freeze Dryer 110V

033180:30C Refrigerating Dryer Air Compressor Refrigerated Freeze Dryer 220V 3.5m3/min

新建网页 2 新建网页 1

15C Refrigerating Dryer Air Compressor Refrigerated Freeze Dryer

Product parameter:

Flow capacity70 cfm
Refrigerant Type
R134A
Voltage
220V
Power
800W
Interface pipe diameter: ZG1.0
Air capacity: 2.5m³/min
Work pressure:
1.0Mpa
Inlet temperature:
80
Dew point temperature: 2-10

Features:
1.Environmental friendly. This machine adopt R134a environmental protection refrigerants, the destruction to the atmosphere is zero and meet the needs of the international market.

2.Easy To Install. Easy installation with the compact design is ready to use with a small footprint,matches the compressor's displacement, saving energyeasy maintenance and improved reliability.
 

Working principle:

The humid and high temperature compressed air flows into the front cooler after the heat exchange into the heat exchanger and the cold air discharged from the evaporator, so that the temperature of the compressed air into the evaporator is reduced.

The air of the heat transfer into the evaporator through the evaporator heat transfer function and refrigerant heat exchange, the heat in the compressed air is taken away by the refrigerant, compressed air rapid cooling, the wet air moisture reaches saturation temperature rapid condensation, condensed water after condensation, after the unique air water separator high speed rotation, water due to the action of the centrifugal force and air separation, after separation of water from the automatic drainage valve. The lowest air pressure dew point after cooling can be up to 2℃ after cooling.

After cooling the cold air flows through the air heat exchange and inlet of hot humid hot air heat exchange, the heat exchange of cold air for absorb the heat, the inlet air and the compressed air through the freezing system of secondary condenser and high temperature refrigerant heat exchange again make the outlet temperature is fully heated, to ensure that the outlet air pipeline is not exposed. At the same time, it makes full use of the outlet air cooling source to ensure the condensation effect of the freezing system and ensure the quality of the outlet air of the machine.

Operation method:

1. Check whether the refrigeration system pressure of the machine is normal. Check that the ball valve at the front of the automatic drainage valve is open.

2. Send the power supply to the control box, press ON/OFF button switch ON button, machine contactor suction, compressor operation. At this time, the refrigerant low pressure gauge pointer should indicate that it is in the range of 60~85Psig. If the load exceeds this range, adjust it.

3. After the compressor runs smoothly, the pressure of the refrigerant high pressure gauge rises to between 120 and 240psi.
When the high pressure of the refrigerant is higher than this range, check whether the heat dissipation of the condenser is good, and whether the inlet temperature of the air compressor and the ambient temperature are too high. When the antifreeze switch is lower than 140Psig, the condensing fan stops running to increase the pressure to ensure the normal operation of the machine. If the machine is operated at low pressure for a long time, check whether the refrigeration system leaks.

4. Please turn off the air compressor before shutting down. After turning OFF the air compressor, press the ON/OFF switch to turn off the power supply of the machine.
 

Note:

1. Please turn on the cold dryer for about 5 minutes before using the gas.

2. It is recommended that the side of the power cable connected to the machine should be against the wall, with the front side at least 1 meter away from the wall and the back side at least 20 cm away from the wall.

3. The drain time can be adjusted. If it needs to be adjusted longer, the SEC key on the left can be adjusted to 2 seconds, and the MIN key on the right can be adjusted to 5 minutes (0-10 middle).

4. Be sure to wrap raw material tape or use liquid sealant when installing.
 


 

1.Different places have different Receptacles. Please note this plug and

consult your electrician before purchase.

2.This machine needs to be connected to the power source for use by the customer.

 

Product structure:

Product display:

Item Number: 1* 15C Refrigerating Dryer Air Compressor Refrigerated Freeze Dryer (239848)

You can make order with no worry.
Any concerns just feel free to let us know, we'll reply in 24 hours in normal condition.
Handling Time: Shipping is usually made in 1-3 business days after payments cleared. Orders are processed from Monday-Friday; Not on the weekends & public holidays.
Warranty: 6 months' warranty for the machines, not for the consumables.
We stand behind our products all the item, so even if your warranty period has expired, you can still seek for service or technical support from us with low cost.

无标题文档

About Us Product Service Shipping Payment Privacy refund Warranty

Copyright eezglobal.com All Rights Reserved